Temperature & Humidity Sensor
A wired temperature and humidity sensor with RS485 / Modbus RTU output, a 5 V DC supply and configurable device address and baud rate
Discuss this modelKey features
- Temperature and humidity readings over RS485 using the standard Modbus RTU protocol, with device addresses and baud rates configurable in PC software.
- Temperature accuracy ±0.5°C at 25°C; humidity accuracy ±4%RH at 25°C within 5%RH–95%RH, with a 1-second update interval.
- Built-in EMC interference suppression and reverse-polarity protection, with maximum power consumption ≤0.05 W from a 5 V DC supply.
Functions in detail
Temperature and humidity measurement
- Resolution of 0.1°C and 0.1%RH; readings update every 1 second.
- Long-term stability: temperature ≤0.1°C/year and humidity ≤1%RH/year.
- At an air speed of 1 m/s, response time is ≤15s for temperature and ≤4s for humidity.
RS485 bus communication
- Standard Modbus RTU with a stated maximum communication distance of up to 2000 m; check the actual cable, topology and site conditions.
- Multiple sensors can share a bus; each device must have a unique communication address.
- Factory settings: 9600bit/s, address 0x01, 8 data bits, no parity, 1 stop bit and CRC checking.
Register access and configuration
- Read humidity at 0000H (PLC 40001) and temperature at 0001H (PLC 40002), using function 03.
- Returned measurement values are multiplied by 10; negative temperatures use two’s-complement representation.
- Device address at 07D0H and baud rate at 07D1H support functions 03 and 06; PC software can read and change these settings.
Power and wiring
- Red wire: 5 V DC positive; black wire: power negative.
- Yellow wire: 485-A; green wire: 485-B. Do not swap A and B.
- The sensor includes EMC interference suppression and power reverse-polarity protection.
Technical specifications
| Parameter | Specification |
|---|---|
| Power supply | 5 V DC |
| Maximum power consumption | ≤0.05 W |
| Humidity accuracy | ±4%RH (5%RH~95%RH, 25°C) |
| Temperature accuracy | ±0.5°C (25°C) |
| Operating environment | -40°C to +80°C; 0%RH~100%RH |
| Communication protocol | Modbus RTU |
| Output signal | RS485 |
| Temperature resolution | 0.1°C |
| Humidity resolution | 0.1%RH |
| Temperature/humidity update interval | 1s |
| Long-term stability | Temperature ≤0.1°C/year; humidity ≤1%RH/year |
| Response time | Temperature ≤15s (air speed 1 m/s); humidity ≤4s (air speed 1 m/s) |
| Configuration method | PC software |
| Encoding | 8-bit binary |
| Data bits | 8 bits |
| Parity | None |
| Stop bits | 1 bit |
| Error checking | CRC |
| Factory baud rate | 9600bit/s |
| Factory device address | 0x01 |
| Wiring: red | Power positive, 5 V DC |
| Wiring: black | Power negative |
| Wiring: yellow | 485-A |
| Wiring: green | 485-B |
| Register 0000H | PLC 40001; humidity ×10; read-only; function 03 |
| Register 0001H | PLC 40002; temperature ×10; read-only; function 03 |
| Register 07D0H | PLC 42001; device address; read/write; functions 03, 06 |
| Register 07D1H | PLC 42002; baud rate; read/write; functions 03, 06 |
Installation and configuration
Use a 5 V DC supply and check the receiving device supports RS485 and Modbus RTU. Follow the wire colours and A/B polarity, assign a unique address to each sensor on the bus, and match the baud rate and serial settings. Confirm readings and register scaling in the connected system before deployment.